The ontario building code manual pull stations 3 2 4 18.
Fire pull station height.
1200 1400 mm above the floor measured to the centre of the manual station the centre of the back box 1050 1150 mm above the floor measured to the centre of the manual station the centre of the back box audible signalling appliance.
In this case height is measured from the floor to the operable part of each manual fire alarm box according to section 5 13 4 of nfpa 72 2007 edition mounting height must be between 3 and 4 feet from floor to handle.
Ada fire extinguisher heights and fire alarm pull station placement must allow wheelchair users access and ease of operation.
Not less than 2300 mm above the floor where ceiling heights allow measured to the centre of the device.
Through a forward reach or a side reach.
This as well as other questions found on this website and our study guides would be a typical question asked on the nicet certification exam.
2 in a building that is sprinklered a manual pull station is not required at an exterior egress.
In a forward reach the wheelchair user approaches the object head on.
Below we have an picture of a typical manual pull station.
But just like pulling the fire alarm may be done to get kids out of class a pull station might look like a get out of jail free card to an inmate.
The ada provides two ways to make operable parts accessible to wheelchair users.
Nfpa 72 the national fire alarm and signalling code requires the operating switch of manual pull stations to be located between 42 and 48 inches from the floor.
Another important aspect associated with device placement involves the height at which it must be mounted.
Manual fire alarm boxes shall be red in color.
Sections 22 3 4 2 and 23 3 4 2 of nfpa 101 require fire alarms to initiate manually as well as by any detection devices that may be required in other parts of the code.